It was a freezing Friday evening early in February 2023, when my boiler broke. An engineer was called, several cold days passed, and his declaration came in sombre tones: ‘uneconomic to repair’. Li…

  • spacecowboy
    link
    fedilink
    English
    arrow-up
    20
    ·
    10 months ago

    I just had one installed in Canada during that -30C > -50C cold snap on the prairies. I paired it up with a backup LNG furnace for the coldest of cold snaps we get. It’s only been a couple of weeks but it has not warmed up enough for the pump to kick over. I plan to keep detailed notes this year to compare data.

    A lot of the people I know and work with think these things are a fad/gimmick/wont work in Canada… I aim to prove them wrong!

  • grue@lemmy.world
    link
    fedilink
    English
    arrow-up
    19
    ·
    10 months ago

    It’s weird that heat pumps are seen as so exotic and complicated when they’re really just air conditioners plus reversing valves.

    • HeartyBeast@kbin.socialOP
      link
      fedilink
      arrow-up
      16
      arrow-down
      2
      ·
      10 months ago
      1. Air conditioners in UK houses are pretty weird and complicated
      2. Potentially having to rip out aall the (usually underfloor) pipe work and replace all your radiator is pretty complicated, compared to switching out the existing gas-fed box on the wall
      3. Working out the capacity needed to heat your home is pretty complicated
      4. Finding the space outside in a small urban garden than can take the unit, without annoying the neighbours next door with the noise can be pretty complicated.
      • GreatAlbatross@feddit.ukM
        link
        fedilink
        English
        arrow-up
        5
        ·
        10 months ago

        The capacity calculations and potential noise complaints are the big ones imho.

        I can definitely see issues with installers not giving a toss about noise, and having to be chased later.

        Calculating capacity isn’t that complicated, you can look everything up to work it out (wmk losses, etc.), but it is a step up from the current “slap a new boiler in” mentality.

        And I wouldn’t be surprised if most heating techs don’t consider requirement at all when changing a boiler, they’ll just put in a big one, and run the rads at 70 if the client complains.

        There is talk about ASHPs that can still maintain efficiency at higher temps, which may help a lot of households avoid changing the radiators too. But it’s still early days.

      • mindbleach
        link
        fedilink
        English
        arrow-up
        5
        ·
        10 months ago

        You can leave the pipes there. They’re not doing much. Radiators aren’t much threat either, unless you trip into one.

        • HeartyBeast@kbin.socialOP
          link
          fedilink
          arrow-up
          5
          ·
          10 months ago

          Not really. Since the radiators operate at a substantially lower temperature, you may well have to replace them - you need larger, more efficient radiators than may be typical with gas-fired systems

          • mindbleach
            link
            fedilink
            English
            arrow-up
            5
            arrow-down
            1
            ·
            10 months ago

            Oh, using the same system, instead of switching to forced air.

            … why does efficiency matter if the heat stays in the house? They’re just always-warm instead of sometimes-hot, yeah?

            • c0m47053@feddit.uk
              link
              fedilink
              English
              arrow-up
              7
              ·
              10 months ago

              We don’t tend to use air/air heat pump systems in the UK, even for new builds, always air/water.

              Because of lower water temperature output of heat pumps compared to the gas boilers they replace, usually you need to increase the size of radiators to be able to achieve a room temperature change in a reasonable time. What is being referred to as efficiently, is actually just a measure of performance of the radiator, not actual energy efficiency.

  • doublejay1999@lemmy.world
    link
    fedilink
    English
    arrow-up
    20
    arrow-down
    1
    ·
    edit-2
    10 months ago

    What an odd way to encourage people to get heat pumps.

    ‘It’s much simpler than you think : Experiment with your flow temperatures, get your pipes widened if necessary, and if that doesn’t work, get on twitter and hope that a random software engineer outside the industry can get you sorted ‘

    • Fudoshin ️🏳️‍🌈@feddit.uk
      link
      fedilink
      English
      arrow-up
      9
      arrow-down
      26
      ·
      10 months ago

      Interesting but not surprising. We live in a 3rd world country. I’m surprised we haven’t got packs of wild proto-humans roaming the streets canabalising innocent people with over a decade of fuck ups.

      We can’t build anything. We can’t fix anything. At this point I think it would be an improvement if Russia invaded or nuked us.

    • wewbull@feddit.uk
      link
      fedilink
      English
      arrow-up
      8
      ·
      edit-2
      10 months ago

      I saw that about at week ago. Seems to be getting pushed in the algorithm.

      The TL; DW for people:

      • The installer didn’t place the heat pump on a solid level base. This resulted in the unit not being level, which caused bearings to wear at a highly accelerated rate. Killed the unit in a couple of years.

      • Hugely over-complicated plumbing install which introduced unnecessary heat exchanging between water loops and mixing of heated & return water. All introduced losses. The unnecessary components in the system just added expense.

      • Due to the unnecessary losses, the heat pump had to run at a higher temperature for the system to work. Hence the heat pump was a much more expensive unit than really needed. (Dual stage with two refrigerants rather than single stage).

      • The water tank used was unsuitable for a heat pump fed system, having too short a heat exchanger for the water temperature being fed to it.

      • The system was set to a fixed temperature with no weather compensation curve. The system was always working as if it was a really cold day, killing its efficiency and putting it under more load than necessary.

      The fix would be to simplify the system and reinstall the unit on a proper base, replacing it with a smaller cheaper one. Basically the guy was completely mis-sold by a dodgy company.