I’m a helper and worked with an old time electrician and he did something a year ago that still troubles me. We wired a 50 amp 220 volt circuit for some heat pumps. he brought the wires into the panel, hooked them to ground and the breaker and left the white wire capped with a wire nut. He told me it will work fine and forget about it. Did we leave somebody with an open neutral? Is the ground wire the neutral now? Should I try and go back and fix this?

  • bobs_monkey@lemm.ee
    link
    fedilink
    English
    arrow-up
    1
    ·
    1 year ago

    It’s the same idea, except with two legs of single phase instead of 3 legs of three phase. A lot of HVAC equipment is centered around some kind of motor, and they’ll typically have some kind of transformer to derive control voltage.