So a circuit in my home is dead. It covers a couple lights and a couple outlets. I plugged a microwave into this circuit and it was more than she could handle. Before this, the circuit worked fine for years, but the lights would noticeably dim when the load from the toaster was applied.
The breaker is not tripped. I replaced the breaker. This particular breaker was different from the others, not labeled on the panel, and the romex enters the panel from a different direction than the other 20amp circuits; I suspect this circuit was added after initial construction.
There is no GFCI on this circuit. The fixtures and outlets are all standard with no obvious fuses. There are no scorch marks, and there was no smell when the circuit cut out.
I worked as an electrician’s assistant when I was a teenager. I have basic skills and basic tools. I don’t have an outlet tester or a mutimeter.
A physical connection has broken somewhere on this circuit, likely because the high current load of your microwave heated up a loose connection somewhere, it melted or arced, and went bang. Now you have an open circuit.
If I were a gambler, I would predict that you will find that one of the contacts on either an outlet or a light switch, or one of their connecting screw terminals, somewhere along the path of that circuit has exploded. Start by checking those first. It will probably be fairly evident where the smoke was generated. If you find wire nuts anywhere in your search, check beneath those as well.
If you are super unlucky you have a break in the conductors in the Romex somewhere. That’s both A) annoying, and B) dangerous, since it’ll be a pain in the ass to find, another pain in the ass to rip out and replace, and a fire hazard if you don’t. This is less likely, because residential wiring is solid copper and is usually quite robust provided it isn’t moved or stabbed with something.
There are probably expensive electrician’s tools to trace for broken wires using inductance or something. Me, the last time I had to play search-for-the-break I just made myself some long-ass multimeter probes, disconnected the hot and neutral of that circuit from the breaker box, and ran around probing all the outlets with the meter in continuity mode until I found the one that didn’t beep.
Thanks for the ideas. I’m leaving the breaker off until I can find out what’s up to avoid the fire hazard.